The significance of measuring flue gas oxygen content in boilers
Flue gas oxygen content is one of the important monitoring parameters for boiler operation and an important basis for reflecting the completeness of combustion equipment and boiler operation. Its value is related to factors such as boiler structure, fuel type and properties, boiler load, operating air distribution conditions, and equipment sealing conditions. The smaller the oxygen content, the smaller the excess air coefficient, indicating that the heat loss due to incomplete chemical combustion and incomplete mechanical combustion increases; the larger the oxygen content, the larger the excess air coefficient, indicating that too much air is being supplied. Excess air causes a decrease in furnace temperature, which not only affects combustion but also carries away a large amount of heat and dust, increasing the calculated results of pollution emission concentration. At the same time, a large air volume also increases the power consumption of flue gas exhaust. Controlling flue gas oxygen content is of great significance to controlling the combustion process and achieving safe, efficient, and low-pollution emissions.
Zirconia oxygen analyzer for blast furnace hot blast stoves
Zirconia oxygen analyzer for blast furnace hot blast stoves in steel plants. Hot blast stoves are characterized by strong vibrations and large pressure fluctuations. The pressure can reach 500 KPa. In view of the characteristics of hot blast stoves, our technicians have overcome various difficulties and developed a shock-resistant and high-pressure zirconia oxygen analyzer for hot blast stoves. Our special zirconia oxygen analyzer has a pressure resistance of 650 KPa.
17
Residual oxygen analyzer for atmosphere protection furnace
Atmosphere protection furnace oxygen content analyzer, primarily applied to: metal material annealing furnaces, bogie furnaces, pusher furnaces, and other heating furnaces. Model: VDK-Q8900
02
27
Common fault analysis and preventive measures of zirconia oxygen analyzer
To ensure the boiler reaches the combustion condition, the power plant introduces the oxygen signal into the combustion automatic control system as a correction signal to control the air volume. This requires that the oxygen content measurement of the boiler flue gas must be accurate and reliable. However, the zirconia oxygen analyzer working in a high-temperature, harsh environment with severe flue gas scouring is prone to failure, so we must strengthen the operation and maintenance of the zirconia oxygen analyzer.
Corrosion-resistant zirconia oxygen analyzer for garbage incineration boilers
Incineration power generation is now widespread. However, zirconia analyzers, used to monitor the incineration conditions of garbage, have extremely short lifespans. The main reason is that the composition of garbage is very complex. The flue gas produced after garbage incineration mainly consists of hydrogen chloride, hydrogen fluoride, nitrogen oxides, dioxins, and a series of other toxic and harmful gases. These gases, together with the large amount of water vapor produced during garbage incineration, can seriously damage the sensors in the oxygen probe. Domestic zirconia analyzers can only be used normally in garbage power plants for 3-4 months, and even the longest lifespan does not exceed half a year before they need to be replaced.
Zirconia oxygen analyzer oxygen potential and oxygen content comparison table
2023 Spring Festival Holiday Arrangement
Dear Customer: As the New Year begins, everything takes on a fresh look. All employees of Anhui Tianfen Instrument Co., Ltd. sincerely thank you for your long-term support and love for our company. We extend our most sincere blessings and greetings to you. In the new year, our company will work even harder to provide you with higher quality products and the most considerate service.
Good luck with your work in 2023
Our company resumed normal operations on January 29, 2023. New and returning customers are welcome to place orders. In the new year, we will provide even better products and services. We have newly launched a high-concentration zirconia oxygen content analyzer with a measurement range of 20.6-99.99% and RS485 output. We also offer a trace oxygen zirconia oxygen analyzer with a measurement range of 0.01ppm-5000ppm and RS485 output.
Daily maintenance, precautions, troubleshooting and handling of zirconia oxygen analyzer
Daily maintenance, precautions, troubleshooting and handling of zirconia oxygen analyzer 1. After putting the instrument into use, why can't the calibration be performed immediately?